Power monitoring
Power monitoring fleet
Cloud archiveWhich station-battery bank to visit next — and why — from the recordings and calibrations you already have.
How a bank's status is decided
- Only from recordings you uploaded: the newest one matched to each bank by the Site and Bank names typed on Battery Watch — exactly, or ignoring case, punctuation and words like “substation”. Anything that matches no bank, or two, stays unassigned.
- Amps are estimates from a unit calibrated on site against a clamp meter. A recording made without a calibration has no amps: the bank shows “No current data” — never a guess.
- Discharging: below −0.5 A est. at the last reading — the battery was carrying the load, so check the charger and AC supply. Float rise: the newest week's float current at least 50% and 0.2 A above the week before, same calibration only — an early sign worth a visit. Stale: no recording in 30 days.
- It does not measure electrolyte level, cell voltage or specific gravity, and it can't tell which cell is weak — only which bank to visit, and why.